The condenser unit(s) solid state relay(s) are powered by the relay
board through the J6 plug located on the upper right corner of the relay
board (Figure 17). L
2
is continuously supplied to the solid state condenser
relay(s) and L
1
is switched by the solid state relay on the relay board with
protection by the 250MA fuse (F15).
During either Chill mode or the Holding mode, L
1
and L
2
is
continuously supplied both to and through the solid state relay on the relay
board, to and through the condenser solid state relay(s), and to the pressure
switch(s) and the compressor(s). Both the solid state relay on the relay
board and the solid state relay(s) for the condenser are powered at all times
and the condensers are cycled by the probes. Line voltage (both L
1
and L
2
)
to the condensing units is protected by the SC15 or SC 20 fuses located in
the relay board enclosure. When the probe temperatures are satisfied, the
relay board de-energizes the solenoid valve(s) which causes the
compressor(s) to pump-down into a vacuum. When the pressure on the
suction line drops to 2PSIG, the pressure switch will open and disconnect
the voltage on L
1
which causes the condenser to shut OFF. When the
probe(s) call for cooling, the relay board re-energizes the solenoid coil(s)
causing the low side pressure to rise. When the pressure increases to 18
PSIG, the pressure switch will close which will supply voltage on L
1
and
turn the condensing unit ON.
NOTE: IF THE SOLENOID COIL DOES NOT CLOSE, THE RELAY BOARD SOLENOID COIL LED IS NOT
ILLUMINATED AND THERE IS NO POWER TO THE SOLENOID COIL, A VARISTOR MUST BE
INSTALLED ACROSS L
1
AND THE RIGHT AND/OR LEFT SOLENOID COIL CONNECTION ON
PLUG J5 (
FIGURE 16).
PRESSURE SWITCH
The pressure switch is opened and closed by means of a capillary tube connected to the suction line
which applies pressure on a diaphragm to open and close the switch. The cut-out setting is 2PSIG and the
cut-in setting is 18PSIG.
NOTE: IF THERE IS A LEAK IN THE REFRIGERATION SYSTEM, THE CONDENSER WILL NOT TURN
ON
ON.
TO TEST THE CONDENSER, JUMP-OUT THE PRESSURE SWITCH. IF THE CONDENSER TESTS
GOOD, REMOVE THE JUMPER, LOCATE AND REPAIR THE LEAK, AND RECHARGE THE SYSTEM.
8.
Figure 17
250MA
FUSE
SOLID
STATE
RELAY
L
1
SUPPLY
VOLTAGE
FROM SOLID
STATE RELAY
ON RELAY
BOARD TO
CONDENSER
SOLID STATE
RELAY(S).
L
1
SUPPLY
VOLTAGE TO
SOLID
STATE
RELAY
ON
RELAY
BOARD.